Tool 01Charge injection calculator
Vibration level to pC and back, for checking a vibration monitor without shaking the sensor.
Check a vibration monitor without shaking the sensor. A piezoelectric accelerometer delivers a charge (pC) proportional to acceleration, so with a charge generator (Coulomb simulator) you inject that charge straight into the monitor input at the 1X frequency of the machine. This tool converts a vibration level at running speed into the peak charge to inject, and an injected charge back into the reading you should see.
Level and speed
Enter the vibration level to simulate (an alarm or trip setpoint, as displacement or velocity) and the running speed of the machine.
Sensor sensitivity
Enter the sensitivity of the accelerometer in pC/g, from its datasheet or calibration sheet.
Inject and compare
Set the charge generator to the pC and the frequency shown in the result, then compare the monitor reading. Monitors with a tracking filter or keyphasor also need a speed signal: simulate it at RPM ÷ divisor.
Vibration level → charge to inject
Injected charge → expected reading
Background: 1X, speed signal divisor, formulas
pC = (velocity [mm/s] × 2π × f [Hz] × sensitivity [pC/g]) / 98101 mil = 0.0254 mm = 25.4 μm | RPM ÷ 60 = Hz
Displacement ↔ velocity:
v = d × 2πfPeak ↔ peak-to-peak: multiply or divide by 2
Tool 02Woodward manuals and software finder
Search woodward.com directly, or start from the document numbers for MicroNet, 505, 5009FT, ProTech and easYgen.
Woodward publishes its manuals, product specifications and service tools on its own site. Search there directly, or start from the document numbers we use most. Each number opens Woodward's search for it, with the current revision and the other languages.
MicroNet, MicroNet Plus and MicroNet TMR What we do on these systems →
| Number | Title | Type |
|---|---|---|
| 26166 V1–V3 | MicroNet Simplex / MicroNet Plus digital control | Technical manual |
| 26167 V1–V3 | MicroNet TMR digital control | Technical manual |
| 03333 | MicroNet Plus control system | Product specification |
| 26479 | MicroNet Plus cyber security manual | Cyber security bulletin |
| 26728 | SIL safety manual (MicroNet) | Technical manual |
| 03375 | MicroNet Safety Module | Product specification |
Steam turbine controls: 505, 505XT, 5009FT, Peak 200 What we do on these systems →
| Number | Title | Type |
|---|---|---|
| 26839 V1–V2 | 505 digital control for steam turbines | Technical manual |
| 35018 V1–V3 | 505XT digital control for steam turbines (single valve, extraction and/or admission) | Technical manual |
| 26518 V1–V4 | 5009FT fault-tolerant steam turbine control | Technical manual |
| 03373 | 5009FT fault tolerant control | Product specification |
| 35051 | Peak200 digital control for steam turbines | Technical manual |
| 03438 | Peak200 digital control for steam turbines | Product specification |
Overspeed protection: ProTech What we do on these systems →
| Number | Title | Type |
|---|---|---|
| 26545 | ProTech-GII overspeed protection device | Technical manual |
| 26709 | ProTech-GII overspeed protection device with voted inputs | Technical manual |
| 03370 | ProTech-GII overspeed protection device | Product specification |
| 85206 | ProTech 203 (no interposing relay) | Technical manual |
| 26712 | ProTech GAP manual | Technical manual |
Generator controls: easYgen and LS-6XT What we do on these systems →
Service tools
| Number | Title | Type |
|---|---|---|
| AppManager | AppManager service tool (current and legacy versions) | Software |
| Control Assistant | Control Assistant service tool (current and legacy versions) | Software |
| 26015 | Woodward Control Assistant software, getting started | Technical manual |
| 26775 | Using Control Assistant & SOS software in place of Watch Window & Servlink software | Technical manual |
Good to know. Woodward splits the bigger manuals into volumes (V1, V2 ...), so search on the number without the volume to see them all. The part number on the control's nameplate or the application number in AppManager is often the quickest way to the right document. Documents and software stay on woodward.com; we only link to them. Finder as a separate page →
Tool 03Thermocouple calculator
Temperature to mV and back for type K, J, E and T, with the reference junction taken into account.
Check a thermocouple input with a mV source, or turn a measured mV into temperature. The tables are referenced to 0 °C, while the input card compensates for the temperature at its own terminals. So the mV to source is the table value at the process temperature minus the table value at the terminals.
Temperature → mV to source
Measured mV → temperature
Background: calibrators, test leads, types
Tool 044–20 mA calculator
Scale a loop current both ways, with the five check points for a loop check.
Scale a 4–20 mA signal both ways for a linear transmitter, and get the 0, 25, 50, 75 and 100 % check points for the loop check sheet.
Process value → mA
Measured mA → process value
| Span | Current (mA) | Value |
|---|
Background: NAMUR NE 43 signal levels
Tool 05Pt100 calculator
Resistance to temperature and back for Pt100, Pt500 and Pt1000 sensors.
Check an RTD input with a decade box, or turn a measured resistance into temperature. For standard platinum sensors to IEC 60751 (alpha 0.00385).
Temperature → resistance
Resistance → temperature
Background: lead resistance and wiring
Tool 06Compressor efficiency and fouling check
LM2500, LM6000 or any axial compressor: efficiency from your own readings, compared with a baseline you keep.
Is the compressor getting dirty, and did the wash help? Take a few readings right after a wash and save them as a baseline. Next time, load that file: the tool tells you which speed to run for each step at today's inlet temperature, and compares efficiency and pressure ratio at the same corrected speed. Save every later check too, clean or dirty, and you build up a history of the engine.
Baseline
Right after a wash, overhaul or new install: enter readings at 3 to 5 steady load steps and save them. The file stays on your own pc.
Same speed
Later: load the file. For each step you see the speed to run at today's inlet temperature. Set the load, let it settle.
Compare and keep
Enter today's readings and see the change against the baseline. Save them as a check: load all files next time and you see the trend.
Engine and units
Saved files if you have them
Load the baseline saved after the last wash or overhaul, plus earlier checks if you want the history. You can select several files at once. No files yet? Go to step 3 and save today's readings as the first baseline.
Readings
Steady state only: no SPRINT, no anti-icing, no load change in the last minutes. One row per load step. Row 1 holds example values: overwrite them with your own.
- Polytropic
- —
- Pressure ratio
- —
- Corrected speed
- —
Results
| Reading | Section | Corr. speed rpm | PR | Isentropic eff. % | Polytropic eff. % | Δ eff. vs base, pts | Δ PR vs base % | Against baseline |
|---|
Background: method, accuracy and what it does not tell you
η isentropic = (h(T2s) − h(T1)) / (h(T2) − h(T1))N / √(T inlet / 288.15 K). The speed to run today is that corrected speed times √(T inlet today / 288.15 K). On the LM6000 the LPC uses N2 and T2, the HPC N25 and T25.RestrictedTools for authorised users
LM2500+G4 and LM5000 tools built on OEM data, with a personal login.
Two more tools are built on OEM data: the LM2500+G4 4B bearing HP recoup orifice tool and the LM5000 VG schedule verification tool. They are available to persons authorised by the OEM, with a personal login.