Overspeed protection is the one turbine function that has to work the first time it is needed.
How I approach an overspeed protection check:
- 1.Separate from the speed control. Own probes, own logic, own trip path.
- 2.Three channels, voted two out of three. One failed channel gives an alarm, two agree and it trips.
- 3.Overspeed and over-acceleration. The rate trip acts before the level is reached.
- 4.Simulated speed test, one channel at a time. The other two keep protecting the unit.
- 5.De-energise to trip. Remove the power and the fuel shut-off valves close.
- 6.Latched and recorded. No reset until the cause is clear.