Keeping the compressor out of surge. Three-quarter view of an aeroderivative gas turbine driving a centrifugal compressor with impeller cutaway, its suction and discharge lines and the recycle loop through cooler and anti-surge valve with the gas flow shown, plus a compressor map, six numbered points GAS TURBINE COMPRESSOR FT PT TT PT TT ASC SUCTION DISCHARGE RECYCLE COOLER FLOW HEAD (PRESSURE RISE) SURGE OP SPEED 01SURGE LINEflow too low, flow reverses 02CONTROL LINEmargin to the surge line 03OPERATING POINTflow, pressure, temperature 04RECYCLE VALVEdischarge back to suction 05START AND STOPopen on start and trip 06SURGE DETECTEDvalve holds until reset

Anti-surge control, in plain words.

A centrifugal compressor needs a minimum flow. Below it the flow breaks down and reverses. That is surge.

How the control keeps it away:

  1. 1.Surge line. The left edge of the compressor map. Past it, the machine is unstable.
  2. 2.Control line. A margin to the right of the surge line. The controller acts here.
  3. 3.Operating point. Calculated live from suction flow, pressure, temperature and head.
  4. 4.Recycle valve. Opens at the control line and sends discharge gas back to suction, normally via a cooler.
  5. 5.Start and stop. Open on start, ramps closed once online, fully open on a stop or trip.
  6. 6.Surge detected. The valve holds a minimum position until the operator resets it.

What do you check first when you commission anti-surge? Valve stroke time, transmitter ranges, or the map?

Compressor train start-up coming and need a controls engineer? Send me a message, happy to support.

Send the start date, estimated duration, scope, systems on site and location. You get availability and an estimate the same working day.

Request availability

Question from purchasing or compliance? Company details, insurance, HSE and quality policies and procedures are on the Working with Telic page.

Remco Petersen
Telic Engineering B.V.
Markenplein 24, 1011 MV Amsterdam
The Netherlands
remco.petersen@telic-engineering.nl
+31 6 51345316
Telic Engineering on LinkedIn
Remco Petersen on LinkedIn