A loop check is not done when the HMI shows a number.
How I approach loop checks on an LM package:
- 1.Start at the sensor, not the terminal. Inject at the field end, so junction box, marshalling and I/O are proven too.
- 2.Tag, range and units the same on the card, in the application and on the HMI.
- 3.Thermocouples: right extension cable and connectors all the way (type K on the LM2500), polarity checked.
- 4.RTD wiring: 3 or 4 wire right through, so lead resistance is compensated.
- 5.Speed and vibration: signal in at the pickup end, conditioner matched to the sensor.
- 6.Alarm and trip: drive every signal through both. Check the action, not only the reading.
What do you check first in a loop check? And what would you add?